NORTH RIVER WATER POLLUTION CONTROL PLANT
New York, NY

WATER TANK,
ALBERTSON WATER DISTRICT

Albertson, NY

WATER TANK,
WESTBURY WATER DISTRICT

Westbury, NY

WARDS ISLAND WATER POLLUTION CONTROL PLANT
New York, NY

BALDWIN WATER
TREATMENT PLANT

Cleveland, OH

NEVERSINK TUNNEL OUTLET STILLING CHAMBERS
Grahamsville, NY

 

 

westbury

The reinforced concrete roof slab of this 120 ft diameter water tank exhibited extensive cracking and concrete spalling. FKC investigated the structural integrity of the concrete slab. Impact-Echo testing revealed that over 50% to 60% of the concrete slab areas were delaminated. Concrete cores verified the extent of slab delamination. Laboratory tests indicated low concrete strength and sulfate attack, and evidence of alkali silica reaction. An engineering report with findings, conclusions and recommendations was issued.

   